Only specific cable types are permitted to be installed in cable trays, as defined by applicable codes. Examples include: Power and lighting cables with tray ratings. maintain spacing or to keep cables in place when the tray is ect the minimum bend ra-dius for cables as they exit the bottom of the cable tray. A rung spacing of 6 to 9 inches (150 to 230 mm) is preferable when the cable tray cont d for instrumentation and control applications that require. Cable tray types, fill rules for single-conductor and multiconductor cables, ampacity derating, separation requirements, and when to use tray vs conduit. Cable tray is the preferred wiring method for industrial facilities, data centers, and large commercial buildings where routing dozens or. Cables rated for different voltages can be installed in the same tray, but those operating above 600 volts must either be of Type MC or separated by a solid barrier from lower voltage cables.